General

Adding rainwater loads

Adding rainwater loads is an iterative process based on the displacement due to Dead Load combined with the amount of water related to one permanent lowest point discharge.

 

The method of calculation is based on the NEN 6702#8.7.1 by:

  • EN 1991-1-6 #4.9 (7):

(7) Actions from rainwater should be taken into account for conditions where there may be collection of water such as ponding effects from, for example, inadequate drainage, imperfections of surfaces, deflections and/or failure of dewatering devices.

  • NEN-EN 1991-1-1:2002/NB: 2006: 6.3.8 Loads induced by rainwater on flat roofs:

(1) Loads induced by rainwater on roofs shall be taken from 8.7.1 of NEN 6702.

 

Selection

Rainwater loads are added on preselected members: "Add rainwater on selection members". If no members are selected in combination with horizontal beams at highest point level,  these members will be considered as a sub selection set: "Add rainwater on flat roof". In other cases no rainwater will be added.

 

Properties

Properties

Definition

Comments

b or d (size discharge), [m]

Relative width/discharge diameter, dependent on the system size of the structure. For example: when the length of the roof-surface with a discharge is 20 m and the total width of the discharge is one meter.  With a system size of five meter the width of the discharge that should be entered will be 1/20*5=250 mm (for every pattern lines)

In case of a pitched roof and in situations in which a camber (with a flat roof) is applied, it is assumed that the registered discharge accounts for the entire (selected) roof, so the water will be on all sides

hnd (lowest point discharge), [m]

Height of discharge above the roof or the height of the eaves:  

dhw (x=0) = dnd  + hnd

 

Position main structure

  • 2D system; the structure "as-is"; no 3D effects
  • 3D syst., 1 field; incl. 3D effects for frame with one pattern lines
  • 3D syst., end field; incl. 3D effects for a frame with several pattern lines, in which the end field will be considered
  • 3D syst., inner fields incl. 3D effects for a frame with several pattern lines, in which the inner field will be considered

3D effects can only be taken into account for flat roofs

Structure system size, [m]

System size main structure

 

Ref. points number

Number of reference points for calculation accuracy of loading structure

 

Camber, [m]

Camber in the center of the selection; additional deformation is constructed triangularly. Camber (upwards) is positive

 

Slope, [%]

If the roof has been modeled under slope it will be considered in the calculation automatically and it is impossible to enter a slope

Camber and slope can be combined

Slope side highest point

Selection: left- or right side of the selection

 

Reference period

Reference period for calculation of rainfall intensity according NEN-EN 1991-1-3+C1+A1#7.2(4)

 

Model factor γM

NEN6702#8.7.1.4: The bending should be calculated as the bending in a final position according to  10.1, in which  the first load should be considered the load resulted from the water level according to 8.7.1.5. and in which the stiffness of the building structure is divided by  γM = 1,3

 

Internal results

Option to save all intermediate steps from the iterate process as a load case in the load sheet. It shows the course of the increase of water during the years